AC30 Load Bank

radiator mounted load bankCapacity
30kW at 400V, 3 phase, in sections of 1, 2 x 2, 5 and 2 x 10kW
15kW at 230V, 1 phase, in steps of 333W

Test voltages
380/415V, 3 phase 50/60Hz
220/240V, 1 phase 50/60Hz

Controls
Integral control panel with hinged weatherproof lid with:
1 – 48mm DIN voltmeter 0-500V
3 – 48mm DIN ammeter 0-80A linear
1 – 48mm DIN frequency meter 45-65Hz
2 – single pole MCB’s for short circuit protection
1 – meter fuse

Resistor Elements
Cressall expanded mesh and mica card elements made from with high-grade nickel-chrome stainless steel with 750V insulation.

Cooling
Fan cooled with four 150mm fans powered from the test load itself. The fans are mounted under the load bank and blow vertically and out through mesh screens on each side.

Input cables and connectors
Two 63A colour coded input connectors to IEC-60309-2 are fitted as standard.

Case
All aluminium, finished in red powder coat, with instructions and warning labels, handles and castors.

Dimensions: 560 x 400 x 840mm high Weight: 30kg complete

Download: Cressall AC30 load bank leaflet

Print Page

Cressall Resistors Ltd, Evington Valley Road, Leicester, LE5 5LZ U.K. Tel: (+44) (0)116 273 3633