dual 30 portable load bankDual 30 Load Bank

Capacity
Dual 120/240: 30kW at 120 or 240V, single phase AC or DC. Sections of 0.5, 1, 2, 4, 8 and 16kW

Dual 240/480: 30kW at 240 or 480V, single phase AC or DC. Sections of 0.5, 1, 2, 4, 8 and 16kW

Controls
Integral control panel with:
Switching: 6 illuminated ‘on’ pushbuttons with DC contactors
6 illuminated ‘off’ pushbuttons
Voltmeter: 0-300V or 0-600V
Ammeter: 0-300A or 0-200A
Indication: LED, ‘Power supply on’
Fuse:1
Banana sockets: 2 x 4mm for output of shunt

Resistor Elements
Expanded mesh and mica card elements wound with high-grade nickel-chrome stainless steel resistance tape with 750V primary insulation.

Cooling
Fan cooled by one 300mm axial fan powered from an external 220/240V supply. The fans are mounted under the load bank and blow vertically through mesh screens on each side.

Ammeter shunt
Rating: 100A = 100mV

Input cables and connectors
Two 2.5m 70mm2 flexible input cables complete with M12 lugs and quick-release connectors.

Case
All aluminium, finished in grey powder coat, with instructions and warning labels. The load bank is fitted with a carrying handle and four omni-directional braked castors.

Dimensions: 500 x 600 x 800mm high: Weight 50kg complete

Download: Cressall Dual 30 load bank leaflet

Cressall Resistors Ltd, Evington Valley Road, Leicester, LE5 5LZ U.K. Tel: (+44) (0)116 273 3633